Motors, switchgear, transformers,
buss-work, and in fact, all electrical
equipment is vulnerable to serious failures
due to single phasing. Single phasing
is the loss or electrical breakdown of one
phase of a three-phase circuit.
If undetected the simple failure grows
and can cause a large loss of equipment.
The degree of protection needed is the subject
of some controversy. Economy is one
factor influencing how much protection is
justified.
Nevertheless, in a Property Loss Prevention
Data Sheet, FM Global says more
serious consideration is needed in view of
the number of losses caused by single
phasing. It says, protection against single
phasing is dependent on more than one
protective device.
Causes of Single Phasing
Causes of a single phase condition on three-phase circuit include a blown fuse, a
broken utility line, a contact failure, a
grounded conductor, or an open thermal
element. Unless properly installed protective
devices operate, the result can be
overheating, arcing, fire, and burning
out of windings, or a chain reaction of
electrical failures.
An ‘‘open phase’’ on a polyphase system
(i.e. motors on the system have available
only a single-phase power) will lead
to trouble. If one line (phase) to a threephase
motor opens while it is running, the
motor may continue to run, but as a single-
phase unit. In this condition, the motor
itself tends to maintain the voltage in
all three phases, but current flow in the
other two phases is higher than usual.
This current will be greater than 1.73
times normal current, with maximum
flow of current dependent upon motor efficiency
and power factor. The poorer the power factor or lower the efficiency, the
greater the current flow during a single
phase condition.
A running motor may stall if carrying
more than 35 percent of its rated load
when single phasing occurs. More frequently
it continues to run as a single
phase motor with part of its winding
drawing excessive current. This current,
if measured by an overload relay, will
trigger the relay to disconnect the motor
before it is damaged.
Overload Relays
Many standard motor starters have
overload relay protection in only two of
the three lines (phases) since this arrangement
usually will detect single phasing in
most circumstances. There are conditions
in which the excess current flows only in
one line, and there is a 33 percent probability
that this will be the unprotected leg.
An overload relay properly applied in
each of the three phases would eliminate
this probability.
If on the same feeder there is more than
one connected load, the voltage generated
by the transformer action in the open
phase will supply power to these single
phase loads. This results in heavier current
flow through the connected two
phases. It is only a matter of time until excessive
overheating will cause burning out
of the winding and damage to connected
wiring and switchgear.
Since the ‘‘dead’’ single phase will always
generate at a voltage close in potential
to the supply voltage, any
phase-failure device which is wholly dependent
on voltage alone will not open
the circuit.
Basic Fault Protection
Protection against single-phasing and
related faults may start with first providing
basic protective devices. Without the necessary
basic protection, other protective
devices cannot function satisfactorily to
recognize faults in the system.
Fuses
The standard fuse: Lacking a built-in
time lag, the standard fuse cannot handle a
700 percent starting current, and at the
same time give the required running overload
protection. If the requirement is only
for short circuit protection, then the standard
fuse is satisfactory.
The time-lag fuse: The time-lag fuse is
used for both overload and short circuit
protection. Careful selection of size is necessary
for reliable protection against short
circuit or ground. This is governed by the
full load current rating of the motor. Fuses
are in themselves one of the causes of single-
phasing since a blown fuse can create
single-phasing in a three-phase circuit. It
is therefore important that other protective
features be incorporated in the circuit.
The dual-element fuse:
The dual-element
fuse is a special fuse incorporating
two elements one of which has the speed
of response required for short circuit protection
and the other will provide running over current protection for the motor windings
with enough time delay to handle the
motor starting current.
Thermal Trip Devices
Thermal overload relays are installed in
the motor controller to provide the required
running over-current protection for the motor.
Where circuit breakers are used for
protection of the motor branch circuit, they
are equipped with thermal time delay trips
to provide the required overload protection
for the conductors and a magnetic trip for
instantaneous tripping on short circuits.
Thermal trips are of the melting alloy
or bimetallic type and are widely used as
protection against single-phasing and motor
overload. The development of heat due
to current flow through a series sensing
device will actuate a toggle and trip the
controller circuit breaker.
If the thermal protection is limited to
only two of the three phases of the controller,
protection against single phasing
is not complete since there is a 33 percent
probability that the overload will occur on
the unprotected leg. FSM
Source: “Protect Electrical Equipment
from Single Phasing and Faults,” an FM
Global Property Loss Prevention Data
Sheet.